Test kit for carbon monoxide detectors

SAFE 400

Test button of carbon monoxide detector (CO) does not test the sensor, but only checks the power batteries, electronic circuits, acoustic and optical signalling.
Vzhledem k tomu, že životnost senzorů detektorů oxidu uhelnatého je často nepředvídatelná, doporučujeme jejich pravidelné ověření provozuschopnosti a funkčnosti pomocí kalibrovaného plynu simulujícího přítomnost oxidu uhelnatého testovací sady SAFE 400. Pokud jste si pořídili detektor CO za účelem ochrany života sebe i svých blízkých, doporučujeme každých šest měsíců provést kontrolu senzoru právě pomocí testovací sady SAFE 400. Jen tak si můžete být jisti, že váš detektor skutečně plní svou život zachraňující funkci.

Main functions

CO

Tests all CO detectors according to EN 50291

Calibrated test gas

Lowest price per test

For 10 complete tests

Test kit components under the can lid

Does not contain harmful CFCs

Overall safe

Sensor and device operability test

Quick and easy to use

Device Description

Verifies the reliability of your CO detector

Testovací sada SAFE 400 pro detektory oxidu uhelnatého je určena k testování funkčnosti detektorů oxidu uhelnatého (CO). Sada se skládá z plechovky s testovacím plynem, kapilární trubičky a praktického fóliového sáčku, který plní funkci izolačního pouzdra. Detektory CO nespouští okamžitý poplach. Senzory CO jsou překalibrovány tak, aby detektor CO spustil poplach od určité koncentrace CO. Izolační pouzdro se používá k tomu, aby se testovací plyn nerozptýlil, ale naopak vytvořil konstantní úroveň plynu, která bude mít za následek aktivaci poplachu detektoru v přiměřeném časovém intervalu. Izolační pouzdro tak umožňuje udržet účinné množství kalibračního plynu simulujícího oxid uhelnatý v okolí senzoru během procesu testování.

Method of conducting the test

Place the CO detector in the foil insulation sleeve. Place the included capillary tube on the plastic atomizer. Insert the tube into the insulation sleeve with the detector and seal the sleeve by tightening the ends of the cords around the perimeter of the insulation sleeve. Do not remove any air that remains in the housing. Pull out the capillary tube and reseal the housing by tightening the cords. The detector sensor should sound the alarm within 3 minutes. If the detector does not alarm, repeat the test after 15 minutes.

Gentle and safe

The test gas included in the kit is completely safe and gentle on your equipment. It does not cause corrosion, does not damage the plastic parts of the detector, does not leave any stains and does not contaminate the detectors themselves in any way. When used properly according to the enclosed instructions, it poses no health risk to humans or pets. You can therefore use it with complete peace of mind and confidence that your equipment and health will remain safe.

Simply effective

This kit is an indispensable tool not only for professionals - service and fire engineers, chimney sweeps or companies specializing in the installation of carbon monoxide and smoke detectors - but also for private users and owners of all types of CO detectors. Anyone who wants to be sure that their equipment works reliably and provides effective protection against this insidious and life-threatening gas will appreciate the simplicity and effectiveness of this kit. So you can always keep the safety of your home and work environment under control.

Technical Specifications

ModelSAFE 400
Test Kit forCarbon monoxide and cigarette smoke detectors
Performing the TestThe detector test is carried out in an insulating bag
Gas Dosing Time3 s
Capacity of the Kit10 tests
Volume400 ml
Operating Temperature0 °C to +50 °C
Operating Humidity Up to 95 % RH without condensation
Storage ConditionsTemperature: 0 °C to +50 °C
Humidity: 5 % to 95 % RH without condensation
Product Weight103 g
Product Dimensions66 mm x 200 mm
Number of Pieces in Carton24 pcs
Carton Dimensions410 mm x 210 mm x 275 mm
Carton Weight2.7 kg
EnvironmentDoes not contain harmful CFCs
UN number1956
CertificationCE
Tested byEQC
EAN Code08595080009002